Item |
Power ratings |
15W |
30W |
60W |
Efficiency (typical) |
77% min. |
80% min. |
78% min. |
Input |
Voltage*1 |
100 to 240 VAC (85 to 264 VAC) |
Frequency *1 |
50/60 Hz (47 to 450 Hz) |
Current |
100V input |
0.45 A max. |
0.9 A max. |
1.7 A max. |
200V input |
0.25 A max. |
0.6 A max. |
1.0 A max. |
Power Factor |
-- |
Harmonic current emissions |
Conforms to EN61000-3-2 |
Leakage current |
100V Input |
0.5 mA max. |
200V Input |
1.0 mA max. |
Inrush current *2 |
100V Input |
25 A max. (for a cold start at 25°C) |
200V Input |
50 A max. (for a cold start at 25°C) |
Output |
Voltage adjustment range *3 |
10% to 15% (with V.ADJ) |
Ripple |
2.0% (p-p) max. (at rated input/output voltage) |
Input variation influence |
0.5% max. (at 85 to 264 VAC input, 100% load) |
Load variation influence (rated input voltage) |
2.0% max. (5 V), 1.5% max. (12 V, 24 V), (with rated input, 0 to 100% load) |
1.5% max. (with rated input, 0 to 100% load) |
Temperature variation influence |
0.05%/°C max. |
Startup time *2 |
100 ms max. (at rated input/output voltage) |
1,000 ms max. (at rated input/output voltage) |
Hold time *2 |
20 ms min. (at rated input/output voltage) |
Additional functions |
Overload protection *2 |
105% to 160% of rated load current, voltage drop, automatic reset |
105% to 160% of rated load current, voltage drop, intermittent operation, automatic reset |
Overvoltage protection *2 |
Yes (a zener diode clamp) *4 |
Yes *5 |
Yes |
Undervoltage alarm indication |
Yes (color: red) |
No |
Parallel operation |
No |
Series operation |
Yes for up to 2 Power Supplies (with external diode) |
Other |
Operating ambient temperature |
Refer to the derating curve in Engineering Data. (with no icing or condensation) |
Storage temperature |
25 to 65°C |
Operating ambient humidity |
25% to 85% (Storage humidity: 25% to 90%) |
Dielectric strength |
- 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
- 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
- 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
- 500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA) (only for 60 W)
|
Insulation resistance |
100 M/min. (between all outputs and all inputs/ PE terminals) at 500 VDC |
Vibration resistance |
- 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
- 10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions (only for 60 W)
|
Shock Resistance |
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions |
Output indicator |
Yes (color: green) |
EMI |
Conducted Emissions |
Conforms to EN61204-3 EN55011 Class B and based on FCC Class A |
Conforms to EN61204-3 EN55011 Group 1 Class B and based on FCC Class A |
Radiated Emissions |
Conforms to EN61204-3 EN55011 Class B |
Conforms to EN61204-3 EN55011 Group 1 Class B |
EMS |
Conforms to EN61204-3 high severity levels |
Approved standards |
- UL: UL508 (Listing; Class 2: Per UL1310), UL60950-1, UL1604 (Class I/Division2)
- cUL: CSA C22.2 No.14 (Class 2), No.60950-1, No.213 (Class I/Division2)
- cUL: CSA C22.2 No.14 (Class 2), No.60950-1, No.213 (Class I/Division2)
- EN/VDE: EN50178 (=VDE0160), EN60950-1 (SELV) (=VDE0805 Teil 1)
- According to VDE0106/P100, IP20 (except terminal block)
|
- UL for standard models: UL508 (Listing; Class 2:Per UL1310), UL60950-1
- cUL: CSA C22.2 No.107.1(Class 2: Per CSA C22.2 No. 223)
- cUR: CSA No.60950-1
- EN/VDE: EN50178 (= VDE0160), EN60950-1
- (SELV) (= VDE0805 Teil 1)
- According to VDE 0106/P100, IP20 (except terminal block)
|
SEMI |
F47-0200 (200 VAC input) |
MTBF *7 |
> 500.000 hrs |
> 250.000 hrs |
Weight |
160g max. |
180g max. |
330g max. |